RS485 Wiring Overview
R
Installation of GRAFIK5000 / GRAFIK6000 / GRAFIK7000 System 11
Wiring Notes:
Two #12 AWG (2.5 mm
2
) wires cannot fit into
most connectors on the RS485 link. Use a
screw on connector (or other approved
connector) to “T-tap” a #18 AWG (1.0 mm
2
)
wire to each connector terminal, as needed.
Make this “T-tap” in the Wallbox in order to
keep the length of the new #18 AWG (1.0
mm
2
) wire(s) as short as possible
Connect the uninsulated Drain/Shield wire(s) to
terminal ‘D’ whenever present. If there is no
terminal ‘D’, connect the two Drain/Shield wires
together, making a continuous shield
throughout the link. If the connector at the end
of the link does not have a ‘D’ terminal,
terminate the shield and let it ‘float’
Do not allow any part of the shield to touch
ground (earth) or any electrical circuitry
CSDs are expected to mount into metal
Wallboxes that are connected to grounded
conduit. Grounding the metal mounting plate
helps keep Electrostatic Discharge (ESD) from
affecting the RS485 link
Control Station
Device (CSD)
connector
Drain / Shield
1 #18 AWG
(1.0 mm
2
)
2 #12 AWG
(2.5 mm
2
)
2 #12 AWG
(2.5 mm
2
)
Approved sources of wire include:
Twisted-Shielded Pair (Data Link) only:
Belden #9461
Alpha #2211
One-cable solutions (Data Link, Control Wiring,
and Sense Line in one cable):
Lutron GRX-CBL-46L-500 (non-plenum)
Lutron GRX-PCBL-46L-500 (plenum)
Belden, Alpha, Liberty, and Signature have
approved cables. Ask for GRAFIK Eye
® Cable