AMX Distributed Audio Controllers Delta Series Spezifikationen Seite 156

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 239
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 155
Chapter 5 Parameters|VFD-B Series
Revision July 2008, BE16, SW V4.08 & V5.00 5-99
The base is Pr.01-00. When in PID feedback control, if | Source of PID reference target -
feedback | > Pr.10-16 and exceeds Pr.10-08 detection time, the AC drive will operate
according to Pr.10-09.
10 - 10 PG Pulse Range Unit: 1
Settings 1 ~ 40000 (Max=20000 for 2-pole motor) Factory Setting: 600
A Pulse Generator (PG) or encoder is used as a sensor that provides a feedback signal of the
motor speed. This parameter defines the number of pulses for each cycle of the PG control.
For PG or encoder feedback an option PG-card is needed.
10 - 11 PG Input
Factory Setting: 00
Settings 00 Disable PG
01 Single phase
02 Forward / Counterclockwise rotation
03 Reverse / Clockwise rotation
The relationship between the motor rotation and PG input is illustrated below:
FWD
CCW
REV
CW
PULSE
GENERATOR
PG
10-11=02
10-11=03
A phase leads B phase
A phase
A phase
A phase
B phase
B phase
B phase
CW
B phase leads A phase
10 - 12 ASR (Auto Speed Regulation) control (with PG only) (P) Unit: 0.1
Settings 0.0 to 10.0 Factory Setting: 1.0
This parameter specifies Proportional control and associated gain (P), and is used for speed
control with PG (encoder) feedback.
NOTE
The parameter can be set during operation for easy tuning.
Seitenansicht 155
1 2 ... 151 152 153 154 155 156 157 158 159 160 161 ... 238 239

Kommentare zu diesen Handbüchern

Keine Kommentare