NetLinx Modules
50
RMS NetLinx Programmer’s Guide
Commands
RMSEngineMod listens for the following commands from the vdvRMSEngine
device.
Commands and Descriptions
'SERVER-[IP/Hostname]'
Set the address of the RMS server. A port
can be specified by adding a colon (:) and a
port number to the end of the IP address or
host name. For example, you can set the
port to 10501 using this command:
'192.168.1.1:10501'.
'?SERVER'
Request the current server settings from
the module.
'CLROOT-[Folder]'
Set the root folder of i!-ConnectLinx for this
room. This command can be used to limit
the portion of the i!-ConnectLinx tree avail-
able to users when configuring room pre-
sets. This command is used when a single
NetLinx master is running more than one
instance of RMS.
'ADD DEV-
[DPS],[Name],[Man],[Model]
Set device info for monitored device. DPS
must be in string form (ex: '5001:1:0').
Name, Manufacturer and Model are
optional.
'ADD NPARAM-
[DPS],[Name],[Threshold],
[Status],[Reset],
[Initial Value],[Min],[Max]'
Add a Number parameter. DPS must be in
string form (ex: '5001:1:0').
Threshold can be any of the following:
>=Value - Greater Than or Equal to Value
<=Value - Less Than or Equal to Value
==Value -Equal to Value
!=Value - Not Equal to Value
<>Value - Not Equal to Value
>Value - Greater Than Value
<Value - Less Than Value
(Value) - Contains Value
)Value( - Does Not Contain Value