Wiring Notes
Grounding: In UL installations where the Speaker Supervision option is enabled, grounding is not
permitted.
If grounding, it is recommended a system common be attached to a cold water pipe,
16ga. at 15 feet. Although cold water pipes have been the standard for earth ground,
it is very common in modern construction that a cold water pipe does not provide an
adequate ground due to the extensive use of PVC and other styles of "plastic" tubing.
The best method for grounding the panel is to locate the panel in an area with easy
access to the power company's earth ground.
Telephone Operation: In the event of telephone operational problems, disconnect the control panel by
removing the plug from the RJ31X (CA38A in Canada) wall jack. We recommend
that you demonstrate disconnecting the phones on installation of the system. Do not
disconnect the phone connection inside the control panel. Doing so will result in loss
of your phone lines. If the regular phone works correctly after the control panel has
been disconnected from the phone lines, the control panel has a problem and should
be returned for repair. If upon disconnection of the control panel, there is still a
problem on the line, notify the telephone company and request prompt repair service.
The user may not under any circumstance (in or out of warranty) attempt any service
or repairs to the system. It must be returned to the factory for all repairs.
Communicator: Connection of the fire alarm signal to a fire alarm headquarters or a central station
shall be permitted only with the permission of the local authority having jurisdiction.
The burglary alarm signal shall not be connected to a police emergency number.
Codes: This equipment should be installed in accordance with National Fire Protection
Association's Standard 72 Chapter 2 (National Fire Protection Association, Battery
March Park, Quincy, MA 02269). Printed information describing proper installation,
operation, testing, maintenance, evacuation planning and repair service is to be
provided with this equipment.
Compliance: This device complies with part 15 of FCC rules. Operation is subject to the following
two conditions: (1) It may not cause harmful interference. (2) It must accept any
interference that may cause undesired operation.
Complies with Part 68 of the FCC rules for direct telephone interconnect.
FCC Registration Number: 107USA-74224-AL-T
Ringer Equivalence: 0.8
Use USOC RJ-31X telephone connection jack. Complies with ANSI/UL 1023
Household Burglary Alarm System Units and ANSI/UL 985 Household Fire Warning
System Units.
Connections: Use UL Listed Cable for all connections.
Testing: Weekly testing is required to ensure proper operation of this system
Servicing: To prevent the risk of shock, disconnect telephone line at telephone company supply
jack before servicing this unit.
Battery: Battery normally need not be replaced for at least 3 years. Use a 12 volt 7Ah battery
(minimum). For all UL installations use two 12 volt 7Ah batteries wired in parallel.