Initial Configuration and Firmware Upgrade
6
NetLinx Integrated Controllers- WebConsole & Programming Guide (FMv3)
Configuring the NI Controller for LAN Communication
Before continuing, complete the COM port steps above.
1. Use an LAN cable to connect the Controller to the LAN to which the PC running NetLinx Studio is
connected.
2. Select Diagnostics > Network Address from the menu bar and enter the System, Device (0 for a
Master), and Host Name information.
3. To configure the Address:
Use a DHCP Address by selecting the Use DHCP radio button, then click the GET IP button (to
obtain a DHCP Address from the DHCP Server), click the SET IP Information button (to retain
the new address), and then finish the process by clicking the Reboot Master > OK buttons.
Use a Static IP Address by selecting the Specify IP Address radio button, enter the IP parameters
into the available fields, then click the SET IP Information button (to retain the pre-reserved IP
Address to the Master), and then click the Reboot Master > OK buttons to finish the process.
4. Repeat steps 1 - 5 from the previous section, but rather than selecting the Serial option, choose TCP/IP
and edit the settings to match the IP Address you are using (Static or IP).
5. Click on the Authentication Required radio box (if the Master is secured) and press the User Name and
Password button to enter a valid username and password being used by the secured Master.
6. Click the OK to close all dialogs and return to the main application.
Using the ID Button to Change the Master Device Value
Use the ID Button on the rear panel (in conjunction with ID Mode function in NetLinx Studio) to establish a
NetLinx Device ID for the device.
The steps described and the dialogs shown in this section are in the NetLinx Studio application.
NetLinx Studio is available to download from www.amx.com.
Refer to the NetLinx Studio on-line help for information on using NetLinx Studio.
1. Access the Device Addressing dialog (FIG. 4) by selecting Diagnostics > Device Addressing.
2. Enter the system number in the Destination System field.
3. Enter the desired device number in the Change to Device box (Device field), and again enter the system
number (in the System field).
The NI-x100 Controllers feature an Auto MDI/MDI-X LAN port. This provides the
option of using either a standard (straight through), or a crossover LAN cable to
communicate with a PC - both cable types will work.
FIG. 4 Device Addressing dialog