Protected Setup Page
76
TPI-PRO/DVI (Total Presentation Interface)
Protected Setup - Calibrate Page
Select Calibrate on the Protected Setup Page (see FIG. 69 on page 71) to access the Calibrate Page (FIG. 71).
The options on this page allow you to calibrate the input touch device (touch monitor) using the selected touch
driver.
If no touch device is detected, the Calibration page is not available. In this case, the TPI-PRO/DVI
will ignore any attempt to open the Calibration page.
If the wrong touch driver is selected prior to the calibration process, press any of the front-panel
pushbuttons to exit the Calibration page (and select a different touch driver).
Press the crosshairs to calibrate the panel.
When the calibration is complete, the Calibrate page closes (returning to the last open
Configuration page).
Refer to the Calibrating the TPI-PRO/DVI section on page 36 for details.
FIG. 71 Calibrate Page
Alternatively, this page can be accessed via the CALIBRATE pushbutton on the front
panel.
If you are using a non-touch enabled monitor, DO NOT PRESS THE CALIBRATE
BUTTON. Refer to the Setting the Output Resolution section on page 34 for screen
adjustment procedures.