Programming the NXB-CCG (for Clear Connect Dimmers and Switches)
16
RPM Device Configuration Guide - NXB-CCG NetLinx Clear Connect Gateway
5. Click in the Level cell to edit the Level value (FIG. 48) .
Note that the default (Dimmer) Level setting for all buttons is 100% (all on). For Button 1, change the value to
"20%", to match Lighting Scene 1, which is 20%.
6. Optionally, click in the Fade cell to edit the Fade value (in seconds). Note that the default Fade setting for all
buttons is 2.00 s (2 seconds).
7. Click Save to save changes.
8. Repeat steps 1-6 for Buttons 2, 3, 4, 5 and 6 (i.e. select and configure "Button 2" under CCT Processor, then repeat
for Buttons 3-6):
Button 2’s Level value should be set to 40%
Button 3’s Level value should be set to 60%
Button 4’s Level value should be set to 80%
Button 5’s Level value should be set to 100% (all on)
Button 6’s Level value should be set to 0% (all off)
Once a Dimmer has been configured for Buttons 1 - 6, the dim (and fade) value specified for each Button will be
activated via the RPM touch panel.
Configuring Buttons 1-6: Adding Switch Functions
Unlike Dimmers, Switches only use two levels: On and Off. Use the Add Device function in the Button Details pages to
add a Switch to Buttons 1-6 if necessary. Once a Switch has been added to a Button, activating the Lighting Scene
associated with each button will turn the switch On or Off:
1. In the Program page, click on Button 1 (under CCT Processor in the Devices window) to open the Button 1 Details
page (see FIG. 45 on page 15).
2. In the Button 1 Details page, click Add Device to open the Add Devices To Button popup (FIG. 49):
3. Select Switch to associate a switch level (On or Off) to Button 1. This setting will cause a press of button 1 on the
touch panel to turn the switch either On or Off.
4. Click Add to add the Switch to Button 1. This action closes the popup and adds the Switch Programming table to
the Button Details page (FIG. 50):
Device Name: The name of the device (Dimmer). The Device Name is read-only.
Level: This is the dim level setting for this button. By default, Level is set to 100%.
Click inside this cell to edit: the dim level value for Button 1 should match the dim level value of
Lighting Scene 1 in RPM (which by default is 20%).
Fade: This is the fade time for this button (in seconds). By default, Fade is set to 2 seconds.
Remove: Click to remove the Dimmer from this Button.
FIG. 48
Dimmer Programming table - Editing the Level value
FIG. 49 Add Devices To Button popup
FIG. 50 Button Details page - Switch Programming table