Lutron® integration protocol
INTEGRATION ID Command Formats
INTEGRATION ID Command-specific fields
Action Numbers and Parameters:
Description Action Number Parameters
Get Integration ID for a Serial
Number
1 Serial Number: 8 character HEX serial number of the device;
Integration ID: The integration ID to be assigned.
Get Info from ID 3 Integration ID = The Integration ID that information is desired for.
Note: If this field is left blank, all integration IDs will be printed.
Example INTEGRATION ID Commands
Operation Command String
Execute: ?INTEGRATIONID, Action Number, Parameters
Get the Integration ID for a serial number ?INTEGRATIONID,1,5678EFEF<CR><LF>
Response: ~INTEGRATIONID, Action Number, Parameters
Get the Integration ID for a serial number ~INTEGRATIONID,1,5678EFEF,1<CR><LF>
Execute: ?INTEGRATIONID, Action Number, Parameters
Get information about an Integration ID command ?INTEGRATIONID,3,1<CR><LF>
Response: ~INTEGRATIONID, Action Number, Parameters
Get information about an Integration ID command ~INTEGRATIONID,3,1,DEVICE,5678EFEF<CR><LF>
Quantum® (continued)
System Commands (continued)
INTEGRATION ID Commands
Use “INTEGRATIONID Command-specific fields” tables
to complete these command fields.
Operation
Command
?INTEGRATIONID, Action Number, Parameters