82
Lutron® integration protocol
Energi Savr NodeTM QS
0 –10 V/Softswitch®/Phase Adaptive (continued)
DEVICE Commands
1
DEVICE Command Formats
iPhone and iPod Touch are trademarks of Apple, Inc., registered in the U.S. and other countries.
H
M
L
QSNE-4A-D
DIN Rail Power Module
230 V~ 50 / 60 Hz 10 A
www.lutron.com
+44.(0)20.7702.0657
Input
S1 S2 S3 S4 CCI
SwitchOccPhotoIR
Type
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
Def
Option
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Zone 1 – Zone 4
1, 2, 3
5 – 8 Set or Get Light Level, Raise, Lower, Stop
Area 1 – Area 4
1, 3
10 –13 Set or Get Scene, Set Light Level, Raise, Lower, Stop
Occupancy Sensor 1 – 4 34 – 37 Report (~) Occupied, Report (~) Unoccupied
Occupancy Sensor 1 – 2 34 – 35 Report (~) Occupied, Report (~) Unoccupied
NOTES
1. Zones and areas are created and configured using the Lutron® ESN Configuration Tool on an iPhone or iPod Touch
mobile device, the Quantum® Q-DesignTM Tool, or the HomeWorks® QS Lutron® Designer. Only those areas and zones
which have been configured using one of these tools are accessible through integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT command. For more details
on setting the output Integration ID of a zone component, see the Integration Access Point section of the system that
contains the ESN.
3. When the ESN is part of a Quantum® or HomeWorks® system, then the #AREA and #OUTPUT commands found in the
Quantum® “System Commands” section of this integration document should be used.
Action Numbers and Parameters:
Action Action Number Parameters
Report (~) Occupied 3 None
Report (~) Unoccupied 4 None
Set or Get Current Scene
1
7 Scene
Scene Save 12 Scene
2
Set or Get Light Level 14 Level = 0 –100 or 0.00 –100.00
Fade
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Delay
3
in: SS.ss
4
, SS, MM:SS, or HH:MM:SS
Set Scene Lock
1
16 0 = Off; 1 = On
Set Sequence State
1
17 0 = Off; 1 = Sequence through Scenes 1– 4;
2 = Sequence through Scenes 5–16
Start Raising 18 None
Start Lowering 19 None
Stop Raising / Lowering 20 None
NOTES
1. QS Standalone only.
2. Available only with Energi Savr NodeTM Firmware > 6.x.
3. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
4. Fractional seconds “SS.ss” will be rounded down to the nearest quarter-second. For example, if a fade time is specified
as 1.31 seconds, a value of 1.25 seconds will be used.
NOTE
1. Not Supported in HomeWorks® QS.
Kommentare zu diesen Handbüchern