Lutron® integration protocol
Energi Savr NodeTM QS
with EcoSystem® (continued)
DEVICE Commands
1
DEVICE Command Formats
iPhone and iPod Touch are trademarks of Apple, Inc., registered in the U.S. and other countries.
Use “DEVICE Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#DEVICE, 5, Component Number, Action Number, Parameters
DEVICE Command-specific fields
Component Numbers:
Component Component Number Available Actions
Occupancy Sensors 1 – 4 136 – 139 Report (~) Occupied, Report (~) Unoccupied
Loop 1 Ballast Occupancy Sensors 140 – 203 Report (~) Occupied, Report (~) Unoccupied
Loop 2 Ballast Occupancy Sensors 204 – 267 Report (~) Occupied, Report (~) Unoccupied
Zone 1–Zone 100
1, 2, 3
1001–1100 Set or Get Light Level, Raise, Lower, Stop
Area 1–Area 100
1, 3
1201–1300 Set or Get Scene, Set Light Level, Raise, Lower, Stop
NOTES
1. Zones and areas are created and configured using the Lutron® ESN Configuration Tool on an iPhone or iPod Touch
mobile device, the Quantum® Q-DesignTM Tool, or the HomeWorks® QS Lutron® Designer. Only those areas and zones
which have been configured using one of these tools are accessible through integration.
2. Assigned zones can be given an individual Integration ID and controlled using the #OUTPUT command. For more details
on setting the output Integration ID of a zone component, see the Integration Access Point section of the system that
contains the ESN.
3. When the ESN is part of a Quantum® or HomeWorks® QS system, then the #AREA and #OUTPUT commands found in
the Quantum® “System Commands” section of this integration document should be used.
Action Numbers and Parameters:
Action Action Number Parameters
Report (~) Occupied 3 None
Report (~) Unoccupied 4 None
Set or Get Current Scene 7 Scene
Scene Save 12 Scene
1
Set or Get Light Level 14 Level = 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set Scene Lock
4
16 0 = Off; 1 = On
Set Sequence State
4
17 0 = Off; 1 = Sequence through Scenes 1– 4;
2 = Sequence through Scenes 5–16
Start Raising 18 None
Start Lowering 19 None
Stop
Raising / Lowering
20 None
NOTES
1. Available only with Energi Savr NodeTM Firmware > 6.x.
2. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second delay.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.31 seconds, a value of 1.25 seconds will be used.
4. QS Standalone only.
NOTE
1. Not Supported in HomeWorks® QS.
Seitenansicht 78