54
Lutron® integration protocol
OUTPUT Command Format
OUTPUT Command-specific fields
Action Numbers and Parameters:
Action Action Number Parameters
Set (#) or Get (?) Output Level 1 Level
1
= 0 –100 or 0.00 –100.00
Fade
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Start Raising
4
2 None
Start Lowering
4
3 None
Stop Raising / Lowering
4
4 None
Pulse 6 Pulse
5
time in: SS.ss
3
, SS, MM:SS, or HH:MM:SS, or
Delay
2
in: SS.ss
3
, SS, MM:SS, or HH:MM:SS
Set DMX color / level settings
6
17 Color / level index: 0 –255
0.00–100.00
5
Motor Jog Raise
6
18 None
7
Motor Jog Lower
6
19 None
7
Motor 4-Stage Jog Raise
6
20 None
7
Motor 4-Stage Jog Lower
6
21 None
7
NOTES
1. The Level is taken as a percentage.
2. The Fade and Delay time are optional. When not used, the system will use a one-second fade time with zero-second
delay. The minimum fade and delay time is 0 seconds. The maximum fade and delay time is 4 hours. For shade outputs,
the Fade parameter has no effect (since shades have fixed speeds) but it is required when specifying an optional delay.
3. Fractional seconds “SS.ss” will be rounded down to the nearest quarter second. For example, if a fade time is specified
as 1.45 seconds a value of 1.25 seconds will be used.
4. When a Raise / Lower command is issued, the output’s level will continue to go towards high end / low end until a Stop
command is received.
5. The default time is one second.
6. Not supported in RadioRA® 2.
7. Quantum® 2.5 and up.
Quantum® (continued)
System Commands (continued)
OUTPUT Commands
Use “OUTPUT Command-specific fields” tables
to complete these command fields.
Operation
Command
Integration ID (example)
#OUTPUT
1
, 2, Action Number, Parameters
NOTE
1. OUTPUT commands can be used to control system lighting zones, contact closed outputs and AC Motor Loads.